Energy Efficiency in Residential Buildings - Standard 100

7/1/2017

0 Comments

 
The ANSI/ASHRAE/IES Standard 100-2015 Energy Efficiency in Existing Buildings provides comprehensive procedures to improve the energy efficiency of buildings. Although Standard 100 provides direction for residential and non-residential buildings, the purpose of this article is to describe the application of Standard 100 to residential buildings.

​The Energy-Use Intensity (EUI) of a building is calculated as the annual net energy use divided by the gross floor area (expressed either as MJ/m2 or BTU/ft2). When calculating the EUI, building energy-use data for twelve consecutive months within the last 18 months must be considered. The energy targets for a building depends on the climate zone in which the building is located. Table 1 shows the climate zone number for major cities in Canada together with the Energy Targets for single-family detached residential buildings. Buildings that meet their energy targets are not required to perform an energy audit.

​Table 1 - Energy Target for Single-Family Detached Homes in Major Canadian Cities
City
Climate Zone
​(Standard 90.1-2016)
Energy Target (MJ/m2)
Energy Target
​(BTU/ft2)
Calgary, AB
7
60
676
Charlottetown, PEI
6A
52
595
Edmonton, AB
7
60
676
Fredericton, NB
6A
52
595
Halifax, NS
6A
52
595
Iqaluit, NU
8
83
944
Montreal, QC
6A
52
595
Ottawa, ON
6A
52
595
Regina, SK
7​
60
676
St. John's, NL
6A
52
595
Toronto, ON
5A
46
519
Vancouver, BC
4C
38
428
Victoria, BC
5C
36
410
Whitehorse, YT
8
83
944
Winnipeg, MB
7
60
676
Yellowknife, NT
8
83
944
Performing an Energy Audit
​In accordance with Standard 100, buildings that do not meet their energy targets are required to undergo an energy audit. As part of the audit, the historical energy use is allocated to end uses such as HVAC, lighting, domestic hot water, and electrical plug loads. Once the energy audit has been completed, the energy efficiency measures (EEMs) to be implemented are selected and the estimated energy savings for the EEMs is calculated. An adjusted EUI is calculated that considers what the EUI would be with the EEMs implemented. Once the adjusted EUI meets the energy target, then the EEMs are implemented.

The energy savings is expressed in both cost units as well as energy units. The cost of implementing each EEM is included together with the simple payback for each EEM or the recommended package of EEMs. Once the EEMs have been implemented, the building's EUI is monitored until twelve consecutive months of data demonstrate that the energy target has been achieved.

​For more information about this topic, please contact us.
0 Comments

    Archives

    June 2018
    February 2018
    January 2018
    November 2017
    July 2017
    June 2017
    May 2017
    April 2017
    March 2017
    December 2016
    November 2016
    October 2016
    September 2016
    January 2016
    August 2015
    July 2015
    June 2015
    March 2015
    February 2015
    December 2014
    November 2014

Copyright 2018 © AirVironment Canada. All rights reserved.
(403) 295-8144 (Calgary) | (780) 655-0948 (Edmonton) | (877) 247-1977 (Rest of Canada)
Click for the BBB Business Review of this Environmental & Ecological Services in Calgary AB
Picture
  • About Us
  • Residential Services
    • Residential IAQ >
      • Mould Testing and Remediation Strategy
      • Asbestos Survey and Monitoring
      • Particulate Monitoring
      • Monitoring for Volatile Organic Compounds
      • Environmental Home Inspections
      • Thermal Imaging
      • Monitoring for EMF
      • Environmental Assessments for Marijuana Grow Operations
    • Building Energy Assessments
  • Industrial Services
    • Occupational Health and Safety Assessments
    • GHG Quantification
    • Environmental Assessments
    • Environmental Analytics and Policy Consulting
    • Project EIAs
  • Your Health
    • Ambient Air Particle Counts
    • Healthy Living
    • Healthy Working
    • Healthy Learning
  • Contact Us
  • Blog